1000 kVA K-13 Harmonic Mitigating Cast Resin Dry-Type Transformer

1000 kVA K-13 Harmonic Mitigating Cast Resin Dry-Type Transformer

1000kVA K-13 rated cast resin dry-type transformer engineered specifically for non-linear harmonic electrical loads in mining VFD drives, solar inverters, and industrial facilities. Conforms to IEEE C57.110, AS/NZS 60076, and IEC 60076-11 with 200% rated neutral conductor and electrostatic shield.

Applications

  • Mining processing plants, conveyor drives, and underground VFD motor controls in Western Australia & Queensland.
  • Solar PV inverter stations, wind farm balance of plant, and battery energy storage system (BESS) connections.
  • Data centers, commercial hospital towers, and telecom facilities with heavy UPS and switching power supply loads.

Features

  • Optimized low-loss foil/transposed winding architecture minimizing stray eddy current losses caused by high-frequency harmonic currents.
  • Heavy-duty 200% rated copper neutral conductor and terminal prevents overheating from 3rd, 9th, and 15th harmonic currents.
  • Grounded copper electrostatic shielding attenuates high-frequency common-mode electrical noise and switching transients.

 

Technical Specifications
Rated Capacity1000 kVA
K-Factor RatingK-13 (Engineered for up to 100% non-linear harmonic load profiles)
Primary Voltage11 kV / 22 kV / 33 kV (AS/NZS & IEC compliant)
Secondary Voltage415V / 240V Three-Phase 4-Wire (Dyn11)
Neutral Busbar Sizing200% Rated Neutral Conductor (Zero-sequence triplen harmonic withstand)
Electrostatic ShieldFull Copper Electrostatic Shield between HV and LV windings
Insulation ClassClass F (155°C) / Class H (180°C) Cast Resin Encapsulated
Cooling MethodAN / AF (Air Natural / Air Forced)
Enclosure RatingIP20 Indoor Steel / IP23 Weather-Protected Enclosure
Standard ReferenceIEEE C57.110 / AS/NZS 60076 / IEC 60076-11 / UL 1561